Chapter 14: Appendices
Appendix 10: NEMA/IP Enclosure Types
(12/99) 14-23
Appendix 10: NEMA/IP
Enclosure Types
The National Electrical Manufacturers Association (NEMA) provides descriptions,
classifications, and test criteria relating to enclosures for electrical equipment. Tables
14-14, 14-15, and 14-16 compare the specific applications of enclosures for indoor
and outdoor nonhazardous locations and indoor hazardous locations.
Provides a Degree of Protection Against Type of Enclosure
the Following Environmental Conditions 1* 2* 4 4X 5 6 6P 12 12K 13
Incidental contact with the enclosed equipment X X X X X X X X X X
Falling dirt XXXXXXXXXX
Falling liquids and light splashing X X X X X X X X X
Circulating dust, lint, fibers, and flyings** X X X X X X X
Settling airborne dust, lint, fibers, and flyings** X X X X X X X X
Hosedown and splashing water X X X X
Oil and coolant seepage XXX
Oil or coolant spraying and splashing X
Corrosive agents X X
Occasional temporary submersion X X
Occasional prolonged submersion X
*These enclosures may be ventilated. However, Type 1 may not provide protection against small particles of falling dirt
when ventilation is provided in the enclosure top. Consult the manufacturer.
**These fibers and flyings are nonhazardous materials and are not considered Class III type ignitable fibers or combustible
flyings. For Class III type ignitable fibers or combustible flyings, see the National Electrical Code, Article 500.
Table 14-14: Specific Applications of Enclosures for Indoor Nonhazardous Locations
Provides a Degree of Protection Against Type of Enclosure
the Following Environmental Conditions 3 3R* 3S 4 4X 6 6P
Incidental contact with the enclosed equipment X X X X X X X
Rain, snow, and sleet** X X X X X X X
Sleet*** X
Windblown dust X X X X X X
Hosedown X X X X
Corrosive agents X X
Occasional temporary submersion X X
Occasional prolonged submersion X
*These enclosures may be ventilated.
**External operating mechanisms are not required to be operable when the enclosure is ice covered.
***External operating mechanisms are operable when the enclosure is ice covered.
Table 14-15: Specific Applications of Enclosures for Outdoor Nonhazardous Locations