Chapter 13: Indicators and Applications
Jaguar Indicator
(12/99) 13-3
Jaguar Indicator
The Jaguar indicator is designed for use with complex automated processing systems. It
offers the greatest range of options for interacting with process equipment.
• Direct PLC Interface for Allen-Bradley RIO, Profibus-DP, or Modbus Plus.
Up to four Jaguar indicators can share one PCB.
Block transfer of floating point and shared data.
Indicator can display messages from PLC.
• Discrete I/O: Four standard inputs and four standard outputs.
Option for 12 inputs and 12 outputs.
12 super setpoints with preact, dribble, and tolerance values.
• BCD Output: Optional 9323 BCD module.
• Analog Output: Optional analog kit with two separate outputs.
• Serial I/O: Two standard serial ports (RS-232/20 mA CL and RS-232/RS-422/RS-
485) and two optional serial ports(RS-232 and RS-232/RS-422/RS-485).
• Filtering: TraxDSP with a very large selection of filtering levels.
• Internal Resolution: 2,000,000 increments.
• Load Cells: Supports up to sixteen 350Ω load cells.
• Enclosures: General purpose, panel mount, and harsh environment.
Lynx Indicator
The Lynx indicator is a reliable scale terminal with strong capabilities for interacting with
process equipment.
• Discrete I/O: Three inputs and five outputs.
Five one-speed setpoints, two two-speed setpoints, or combination.
• BCD Output: Optional BCD kit.
• Analog Output: Optional analog kit.
• Serial I/O: Three bidirectional serial ports (RS-232/RS-485, RS-232/20 mA CL, and
RS-422).
• Filtering: TraxDSP with a large selection of filtering levels.
• Internal Resolution: 2,000,000 increments.
• Load Cells: Supports up to eight 350Ω load cells.
• Enclosures: Panel mount and harsh environment.
LynxBatch Indicator
The LynxBatch indicator has the same basic features as the Lynx indicator, plus a wide
range of capabilities for controlling batching processes.